VRV/VRF System Pipe Sizing
Course Title:
VRF / VRV System Design and Pipe Sizing (Daikin)
Module 1 – Introduction
VRF (Variable Refrigerant Flow) definition
VRV (Variable Refrigerant Volume) definition
Terminology difference (VRV patented by Daikin)
Applications & benefits
One outdoor can connect >60 indoor units
Module 2 – Components & Refrigerants
Compressors:
Digital Scroll Compressor
Inverter Scroll Compressor
Refrigerants: R-410A, R-407C, R-32, R-454B
VFD (Variable Frequency Drive) operation
Power frequency relation to compressor speed
Module 3 – System Types
Cooling Only VRF
Variable speed scroll compressor
Electronic Expansion Valve (EEV)
Heat Pump VRF
Cooling or heating (not simultaneous)
Uses 4-way Reversion Valve & NRV
Heat Recovery VRF
3-pipe system
Cooling & heating simultaneously
Module 4 – Capacity & Piping Limits
Capacity range: 3 TR to 42 TR (10 kW to 150 kW)
Max piping length (Daikin example):
150 m same level
50 m ODU above IDU
40 m ODU below IDU
Daikin pipe sizing conditions:
Max total length = 1000 m
Max equivalent length = 190 m
Max 13 m branch to last ODU
Max 90 m from first indoor branch to farthest IDU
Max level difference ODU–IDU = 90 m
Max level difference IDUs = 30 m
Max level difference ODUs = 5 m
Module 5 – Diversity Factor
Concept in VRF design
Not all IDUs run at full load simultaneously
Example: 20 HP total indoor load with 15 HP ODU
Module 6 – Design Process (Daikin Example)
1. Collect project requirements – building survey
2. Perform heat load calculation (E-20 Excel, HAP)
3. Select indoor units (IDUs)
4. Select outdoor unit (ODU)
5. Design refrigerant piping layout in AutoCAD
6. Perform pipe sizing (manual or software)
Module 7 – Pipe Sizing Basics
Purpose:
Ensure correct refrigerant flow
Avoid oil return issues
Maintain performance & efficiency
Pipes: liquid, gas (suction), discharge (heat recovery)
Refnet joints/Y-branch connectors
Pipe sizing rules:
Size increases after each branch
Different for horizontal/vertical
Long run adjustments (>40 m) require 1-step larger pipe
Module 8 – Manual Pipe Sizing Steps (Daikin)
1. Verify pipe conditions
2. Find CI of indoor units & update on Refnet
3. Size pipe between Refnet & IDU (Table 5)
4. Size pipe from ODU to first Refnet (Table 9 or 10)
5. Size pipe between Refnet to Refnet (Table 6 or 7)
6. Select outdoor branch kit (Table 4)
7. First Refnet from branch kit (Table 3)
8. All other Refnet updates (Table 2)
Module 9 – Common Issues from Wrong Pipe Sizing
Poor cooling/heating
Oil return failure → compressor damage
Refrigerant pressure drop → efficiency loss
System alarms/trips
Khám phá thêm các khoá học cùng chủ đề
ecobiru.com Learning Space (Japan)
Amir Karami • BIM
United Engineering
ExpertEase Global
Augmintech Education Pvt Ltd
ExpertEase Global
ExpertEase Global
Arijit Mukherjee
ExpertEase Global
ExpertEase Global
ASSEM BATTIKH
United Engineering
BIM it! AEC
Tayseer Almattar
Mufaddal Rasheed
Tayseer Almattar
Lluís Foreman - ValueKnow
ExpertEase Global